DESCRIPTION Of THE TERMINALS
6.3.1.1 External supply of the control board
Using the external supply, the control board, I/Os, fieldbus, sensors (temperatures, hu-
midity, mounting orientation) and the interior fan (of 18/19P6) remain in operation even
if the power unit is disconnected.
U
Figure 39:
External supply of the control board
6.3.1.2 Digital outputs
All outputs are short-circuit proof. They are suitable for inductive loads (without free-wheel-
ing diode up to 300 mJ max.). The sum of the load currents at the 24 V outputs of the
control card (DO 0...DO 8, X2B.1/3...31 and X3A und X3B) must not exceed 3.4 A.
DO 0...7
0V
Figure 40:
Digital outputsDO 0...DO 7
DO 8
0V
Figure 41:
Digital output DO 8
62
Terminals
U
in
X2A.35
X2A.36
Others
Current consumption:
Own use 0.65 A
0Vin
+ load currents at DO 0 ... DO 8
+ load currents at X2B.1/3 ... 31
+ load currents at X3A and X3B
Terminals
I
L_max
X2A.18/20...32
X2A.17/19...31
Terminals
I
L_max
X2A.34
X2A.33
Specification
0Vin
: 24 V ±10 %
U
in
Uin
Specification
DO 0...7
: 24 V
U
dc
0 V
: 250 mA
I
L_max
Specification
DO 8
: 24 V
U
dc
0 V
: 2 A
I
L_max