Calculating Settings For Four Step Residual Overcurrent Protection Zero Or Negative Sequence Direction Ef4Ptoc(51N_67N) - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 3
REL650 setting examples
3.1.10
70
source impedance at line end A should be maximized (minimum short circuit power)
for this calculation. We get the phase current If
To assure that step 3 detects all short circuits on the adjacent lines out from the local
busbar a phase-phase short circuit is applied at fault points 9 and 10. The source
impedance at line end B should be maximized (minimum short circuit power) at this
calculation. Resulting phase current is I
Delay of I> should be set larger than the delay of distance protection zone 2
(normally 0.4 s), this means normally at least 0.8 s.
Step 3 should be set so that the maximum load current out on the line does not give
unwanted trip.
The maximum load current can be estimated as:
S
=
=
I
max
Load
,max
×
3
V
min
2142-ANSI V1 EN
The current setting of step 2 is, if possible, chosen as:
I
×
Load
,
max
£
1
2 .
I
h
step
GUID-C3C741A6-8E7B-4E1E-803A-8BC5CD82831C V1 EN
840
×
£
£
1
2 .
I
step
3
. 0
95
GUID-871F169F-1B5E-43C5-8628-1E010031999B V1 EN
where ƞ is the reset ratio of the overcurrent function. For the overcurrent function in
the IED, ƞ = 0.95.
In this case it is not possible to fulfil the requirement above. Priority is given to
selectivity, choosing setting 1100 A and accepting that the phase overcurrent
protection cannot act as remote back-up protection for the remote lines.
2.
Set t3 to 0.8 s
Calculating settings for four step residual overcurrent
protection, zero or negative sequence direction
EF4PTOC(51N_67N)
The residual overcurrent protection is more difficult to set as the ground-fault current is
highly dependent of the network configuration in the power system. In order to achieve
setting that assure selective fault clearance a large number of calculations have to be made
with different fault locations, different switching states in the system and different
ground-fault types. Below one example of setting of four step residual overcurrent
protection for a line in a meshed solidly grounded system is given.
fault9,10,min
180
=
0.84
kA
×
×
3 0.9 138
£
×
0
7 .
min(
I
3
fault
, 7
, 8
, 9
10
×
£
0
7 .
460
or
1061
1MRK 506 334-UUS A
= 0.46 kA
ault7,8,min
= 0.46 kA
)
min
£
I
322
step
3
Application manual
(Equation 21)
(Equation 22)
(Equation 23)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents