Connecting Current And Voltage Inputs - ABB Relion 650 Series Installation Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 514 014-UUS A
6.4.1

Connecting current and voltage inputs

Connect the wires from the CTs to the correct device according to the phase order and the
connection diagram. Each terminal for CTs is dimensioned for one 10 Gauge wire or for two wires
of maximum 12 Gauge.
To help connecting the current and voltage inputs, the connector pair is marked with symbols. For
a current input, the connector pair forms a circle. But in the case of a voltage input, the connector
pair forms two half-circles.
GUID-61D346C6-30D8-468A-8641-654864811C53 V1 EN-US
Figure 16: CTVT connector symbols
1 VT symbol
2 CT symbol
Table 3:
Terminal
X101-1, 2
X101-3, 4
X101-5, 6
X101-7, 8
X101-9, 10
X102-1, 2
X102-3, 4
X102-5, 6
X102-7, 8
X102-9, 10
650 series
Installation manual
Analog input modules
TRM
6I + 4U
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
100/220V
100/220V
100/220V
100/220V
See the connection diagrams for information on the analog input module variant
included in a particular configured IED. The primary and secondary rated values of
the primary VT's and CT's are set for the analog inputs of the IED.
© Copyright 2011 ABB. All rights reserved
TRM
TRM
8I + 2U
4I + 1I + 5U
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
0.1/0.5A
1/5A
100/220V
1/5A
100/220V
1/5A
100/220V
100/220V
100/220V
100/220V
100/220V
Section 6
Connecting
GUID-00D2DE80-9DA7-45FB-AB5B-98E89E3A9220 v2
AIM
AIM
6I + 4U
4I + 1I + 5U
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
0.1/0.5A
1/5A
100/220V
100/220V
100/220V
100/220V
100/220V
100/220V
100/220V
100/220V
100/220V
35