Section 5
GOOSE
5.5
50
5.
Open the SCL file exported from IET600.
6.
In the SCL Import Options dialog box under IED Types, select Don't import
IEDs of unknown type if the GOOSE configuration does not include third-
party devices.
GUID-1EDEA175-63B8-4681-A067-66A797AD204C V1 EN
Figure 32:
SCL import options in PCM600
7.
Click Import.
For more information, see the PCM600 documentation.
Connecting GOOSE inputs to a relay application
1.
In PCM600, open Project Explorer and select the Plant Structure tab.
2.
Add the GOOSERCV function block with the Application Configuration tool.
The GOOSERCV function block can only be added with the
Application Configuration tool.
Give the GOOSERCV block application-specific user-defined
names to distinguish between different blocks when making
GOOSE connections in the Signal Matrix tool.
1MRS757809 C
REC615 and RER615