Section 3
REF615 standard configurations
3.3.3.4
66
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_ALARM
TCSSCBR2_ALARM
GUID-F6281256-8B8D-41D9-AD19-014D604AFCEC V1 EN
Figure 36:
Trip circuit supervision function
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
GUID-F0B3AFC4-7D62-49A3-BF0D-AD03041EA78D V1 EN
Figure 37:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated using the configuration logic, which is based on the status of the
trip logics. However, other signals can be connected based on the application needs.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_ENA_CLOSE
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
GUID-FD60A0AB-713C-461F-BB52-7195A5AD23DA V2 EN
Figure 38:
Circuit breaker control logic: Circuit breaker 1
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
O
B2
OR6
B1
O
B2
B3
B4
B5
B6
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
1MRS756378 S
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR_ALARM
TCSSCBR_BLOCKING
CBXCBR1_SELECTED
CBXCBR1_EXE_OP
CBXCBR1_EXE_CL
REF615
Application Manual