Cable - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

9.3.3
RS-485 cable
Connection diagram
RS485 connection diagram 1)
* 1
GOT side
SDA1(TXD1+)
1
SDB1(TXD1-)
2
RDA1(RXD1+)
3
RDB1(RXD1-)
4
SDA2(TXD2+)
5
SDB2(TXD2-)
6
RDA2(RXD2+)
7
RDB2(RXD2-)
8
RSA(RTS+)
9
RSB(RTS-)
10
CSA(CTS+)
11
CSB(CTS-)
12
SG
13
NC
14
Shell
*1
Set the terminating resistor of GOT as follows.
GT16: Set the terminating resistor setting switch of the GOT
main unit to "100 OHM".
■ Connecting terminating resistors
*2
For details of the pin assignment, refer to the following
manual.
User's Manual of the RKC temperature controller
RS485 connection diagram 2)
* 1
GOT side
(terminal block)
SDA1
1
SDB1
2
RDA1
3
RDB1
4
SDA2
5
SDB2
6
RDA2
7
RDB2
8
SG
9
FG
10
*1
Set the terminating resistor of GOT as follows.
GT16,GT15: Set the terminating resistor setting switch of the
GOT main unit to "100 OHM".
■ Connecting terminating resistors
*2
For details of the pin assignment, refer to the following
manual.
User's Manual of the RKC temperature controller
9 - 30
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.3 Connection Diagram
RKC temperature controller side
* 2
(Modular connector)
T/R(B)
2
T/R(A)
1
NC
4
NC
5
SG
3
SG
6
RKC temperature controller side
* 2
(Modular connector)
T/R(B)
2
T/R(A)
1
NC
4
NC
5
SG
3
SG
6
RS485 connection diagram 3)
* 1
GOT side
(terminal block)
SDA1(TXD1+)
6
SDB1(TXD1-)
8
NC
1
SG
2
NC
3
NC
4
SDA2(TXD2+)
5
SDB2(TXD2-)
7
RDA2(RXD2+)
9
RDA1(RXD1+)
10
RDB2(RXD2-)
11
RDB1(RXD1-)
12
NC
13
RSA(RTS+)
14
NC
15
RSB(RTS-)
16
NC
17
CSA(CTS+)
18
NC
19
CSB(CTS-)
20
*1
Set the terminating resistor of GOT as follows.
GT16: Set the terminating resistor setting switch of the GOT
main unit to "100 OHM".
■ Connecting terminating resistors
*2
For details of the pin assignment, refer to the following
manual.
User's Manual of the RKC temperature controller
RS485 connection diagram 4)
* 1
GOT side
(terminal block)
SDA1
1
SDB1
2
RDA1
3
RDB1
4
SDA2
5
SDB2
6
RDA2
7
RDB2
8
SG
9
FG
10
*1
Set the terminating resistor of GOT as follows.
GT16,GT15: Set the terminating resistor setting switch of the
GOT main unit to "100 OHM".
■ Connecting terminating resistors
*2
For details of the pin assignment, refer to the following
manual.
User's Manual of the RKC temperature controller
RKC temperature controller side
* 2
(Modular connector)
T/R(B)
2
T/R(A)
1
NC
4
SG
3
NC
5
SG
6
RKC temperature controller side
* 2
(Modular connector)
T/R(B)
2
T/R(A)
1
SG
3
N.C.
4
N.C.
5
SG
6

Advertisement

Table of Contents
loading