Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Ethernet setting
6 - 22
6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
(2) GT15, GT12
Item
Description
Set the network No. of the GOT.
GOT NET No.
(Default: 1)
Set the station No. of the GOT.
GOT PLC No.
(Default: 1)
GOT
Set the IP address of the GOT.
IP Address
(Default: 192.168.0.18)
Set the subnet mask for the sub
network.(Only for connection via
Subnet
router)
Mask
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
Default
connected.(Only for connection via
Gateway
router)
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for Ethernet
Download
download.
Port No.
(Default: 5014)
Set the GOT port No. for the
GOT
connection with the connected
Communication
equipment.
Port No.
(Default: 5016)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times
out.
(Default: 3times)
Specify the time period from the
GOT startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
Delay Time
PLC.
(Default: 0ms)
Range
1 to 239
1 to 64
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
1024 to 5010
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
1024 to 5010
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
(
10 ms)