Connecting To Interface Converter (Si-30A) - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(2) Settings of DCE/DTE, RS-422/485 and terminating
resistor selection
Setting item
Set value
DCE/DTE
DCE
RS-422/485
RS-485
Terminating resistor
OFF
selection
5.5.5
Communication settings
DCE-DTE
Make the communication settings using setting
422-485
switches.
TERMINATOR
ON-OFF
Transmission speed
MANUAL-AUTO
DCE/DTE switching
Terminating resistor
*1
selection
*1
Settings by switch
DCE/DTE switch
(1) Settings of transmission speed, MANUAL-AUTO
and terminating resistor selection
Setting item
Transmission
speed
MANUAL-AUTO
Terminating
resistor
selection
*1
(2) Setting of DCE/DTE switching
Setting item
DCE/DTE
5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.5 Temperature Controller Side Setting
Connecting to interface
converter (SI-30A)
Item
Set value
9600bps
AUTO
DCE
ON/OFF
Set as necessary.
RS-232C/RS-485
CONVERTER
RS-232C
DTE
DCE
SW A
RS-485
DRIVER
SD/RD
ACTIVE
B
A
SG
AC 100V FG
Switch No. of DIP SWB
Set value
1
2
9600bps
ON
ON
AUTO
Enable
Disable
*1
Set as necessary.
Set value
DCE
1
2
3
4
DIP SW B:
Communication
setting switch
5
6
3
4
5
OFF
ON
ON
OFF
7
8
5 - 15

Advertisement

Table of Contents
loading

Table of Contents