Connecting To Cb Series; Connecting To Fb Series - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(3) Unit address settings
Set the unit address using the unit address setting
switch.
COM
(4) Interval time settings
Configure the interval time setting using the RKC
communication setting tool (WinPCI).
After the communication is started, set as follows.
Setting item
Instrument
CFG file
Communication 1 interval time
Communication 2 interval time
For the using method of RKC communication setting
tool, refer to the following.
RKC communication setting tool user's manual
9.5.5

Connecting to CB Series

(1) Communication settings
Item
*1
1 to 99
Device address
2: 9600bps
*2
Communication speed
3: 19200bps
0: 8/1/None
Data bit configuration
6: 8/1/Even
7: 8/1/Odd
Interval time
0 to 150
*1
When the setting value is set to 0, a communication is not
made.
*2
Adjust the settings with GOT settings.
(2) Communication setting mode
Set the communication setting mode using the
operation panel of the CB series main unit.
For details of the communication setting mode, refer to
the following.
CB series "Communication Instruction Manual"
Unit address setting switch
Setting range : 0 to F
Set value
0
ZCOM_rkc.cfg
0 to 250ms
Setting range
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5.6

Connecting to FB Series

(1) Communication settings
*1
Item
Communication protocol
1: MODBUS
Device address
1 to 99
*2
(Slave address)
96: 9600bps
*3
19.2: 19200bps
Communication speed
38.4: 38400bps
Data bit configuration
(2) Refer to the data bit configuration.
Interval time
0 to 250
*1
Items and setting range are common to communication 1
and communication 2.
*2
When the setting value is set to 0, a communication is not
made.
*3
Adjust the settings with GOT settings.
(2) Data bit configuration
Set value
Data bit
8n1
8
8n2
8
8E1
8
8E2
8
8o1
8
8o2
8
(3) Communication setting mode
Set the communication setting mode using the
operation panel of the FB series main unit.
For details of the communication setting mode, refer to
the following.
FB series "Communication Instruction Manual"
9.5 Temperature Controller Side Setting
*1
Setting range
Parity bit
Stop bit
None
1
None
2
Even
1
Even
2
Odd
1
Odd
2
9 - 43
9
10
11
12
13
14
15
16