Got Side Settings - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(2) Precautions when preparing a cable
(a) Cable length
The length of the RS-422 cable must be 1200m or
less.
(b) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(c) YOKOGAWA PLC side connector
Use the connector compatible with the
YOKOGAWA PLC side module.
For details, refer to the YOKOGAWA PLC user's
manual.
(3) Connecting terminating resistors
(a) GOT side
When connecting a PLC to the GOT, a terminating
resistor must be connected to the GOT.
• For GT16, GT15, GT12
Set the terminating resistor setting switch of the
GOT main unit to "Disable".
• For GT14, GT11
Set the terminating resistor selector to "330 ".
For the procedure to set the terminating resistor,
refer to the following.
1.4.3 Terminating resistors of GOT
(b) YOKOGAWA PLC side
When connecting a PLC link module to a GOT, a
terminating resistor must be connected to the PC
link module.
The following describes how to connect it on the
PC link module.
• F3LC11-2N
Set the terminator switch (TERMINATOR) on the
front panel of F3LC11-2N to the "4-WIRE" side to
enable the terminator.
• LC02-0N
Connect the terminating resistor provided with the
LC02-0N across SDA and SDB, and across RDA
and RDB on the terminal block.
7 - 8
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
7.2.5

GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller Type: Set either of the followings.
FA500/FA-M3
STARDOM/FA-M3
• I/F: Interface to be used
• Driver: YOKOGAWAFA500/FA-M3/STARDOM
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
7.2.5■Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3.
4.
Click!
[Controller Setting] from the

Advertisement

Table of Contents
loading

Table of Contents