Connecting To Z-Com - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

(3) Unit address settings
Set the unit address using the unit address setting
switch.
(4) Interval time settings
Configure the interval time setting using the RKC
communication setting tool (WinPCI).
After the communication is started, set as follows.
Setting item
Instrument
CFG file
Interval time
For the using method of RKC communication setting
tool, refer to the following.
RKC communication setting tool user's manual
9 - 42
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
Module address setting switch
Setting range : 0 to F
Set value
0
ZTIO_rkc.cfg
0 to 250ms
9.5.4

Connecting to Z-COM

(1) Communication settings
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol
Host (MODBUS)
Data bit
8bits (fixed)
Parity
None (fixed)
Stop bit
1bit (fixed)
*2
0 to F
Unit address
Interval time
0 to 250ms
Dip switch settings
valid
valid / invalid
*1
Adjust the settings with GOT settings.
*2
Select the unit address without overlapping with that of other
units.
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol.
COM
COM.
PORT1
COM1
COM.
PORT2
COM.
PORT3
COM2
COM.
PORT4
Front side
Setting item
Set value
1
9600bps
ON OFF
Communication
speed
19200bps OFF ON
(COM1)
38400bps
ON
Communication
Host
protocol
(MODBUS)
(COM1)
Communication
9600bps
speed
19200bps
(COM2)
Communication
Host
protocol
(MODBUS)
(COM2)
Dip
switch settings
valid
valid / invalid
Setting range
Dip switch
OFF ON
Right side
Switch position
2
3
4
5
6
7
ON
ON
OFF
ON
ON OFF OFF
8
OFF