8.5.5
Connecting to RS232C/RS485
converter (ML2-[])
Communication settings
Make the communication settings using setting switches.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*2
2-wire type or 4-wire type
Setting (2-wire/4-wire)
*2
With, Without
Terminating resistor
Echo back
OFF
RS-485 driver-active control AUTO
*1
Adjust the settings with GOT settings.
*2
Refer to the following connection diagram for setting.
8.3.2 RS-485 cable
Settings by switch
Timer change-over time
Rotary switch
Communication setting
DIP SW
(1) Settings of the setting (2-wire/4-wire), the RS-485
driver-active control, the terminating resistor, the
echo back
Make those settings by operating the communication
setting DIP SW.
Set
Setting item
value
4-wire
type
Setting(2-wire/4-wire)
2-wire
type
RS-485 driver-active control
AUTO
with
Terminating resistor
without
Echo back
OFF
(2) A setting of the transmission speed
Make this setting by operating the timer change-over
time Rotary switch.
Switch position
Transmission speed
5
9600bps
6
19200bps
7
38400bps
Set value
Switch position
1
2
3
4
5
6
OFF OFF
ON
ON
OFF
ON
OFF
OFF