Connecting To Rb Series; Connecting To Pf900/900; Connecting To Ha400/401, Ha900/901 - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

9.5.7

Connecting to RB Series

(1) Communication settings
Item
Communication protocol
1: MODBUS
Device address
1 to 99
*1
(Slave address)
2: 9600bps
*2
Communication speed
3: 19200bps
Data bit configuration
(2) Refer to the data bit configuration.
Interval time
0 to 250
*1
When the setting value is set to 0, a communication is not
made.
*2
Adjust the settings with GOT settings.
(2) Data bit configuration
Set value
Data bit
0
8
1
8
2
8
3
8
4
8
5
8
(3) Communication setting mode
Set the communication setting mode using the
operation panel of the RB series main unit.
For details of the communication setting mode, refer to
the following.
RB series "Communication Instruction Manual"
9.5.8

Connecting to PF900/900

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
9600bps, 19200bps, 38400bps,
*1
Communication speed 1
57600bps
Communication protocol 1 MODBUS
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration 1
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address 1
1 to 99
(Slave address 1)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
9 - 44
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
Setting range
Parity bit
Stop bit
None
1
None
2
Even
1
Even
2
Odd
1
Odd
2
Setting range
*4
9.5.9
Connecting to HA400/401,
HA900/901
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(Communication 1)
Item
*1
9600bps, 19200bps, 38400bps
Communication speed 1
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration 1
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address 1
1 to 99
(Slave address 1)
*3
0 to 250 (ms)
Interval time
(Communication 2)
Item
*1
9600bps, 19200bps, 38400bps
Communication speed 2
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration 2
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address 2
1 to 99
(Slave address 2)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1/2 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
Setting range
*4
Setting range
*4