(2) Data format setting switch
Set the data length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
For the settings on the GOT side, refer to the following.
7.2.5 ■ Communication detail settings
Switch No.
1
Data bit
2
Parity
ON
OFF
3
1
2
3
4
5
4
Stop bit
6
7
8
5
Checksum
End character
6
specification
7
Protect function
8
(3) Station No. switch (LC02-0N only)
Rotary
switch
2
3
1
4
0
5
9
6
Station No.
8
7
1)
STATION NO.
(10's digit)
2
3
1
4
Station No.
0
5
2)
9
6
8
7
(1's digit)
Description
Settings
ON (8bits),
OFF (7bits)
ON (done),
OFF (none)
ON (even),
OFF (odd)
ON (2bits),
OFF (1bit)
ON (done),
OFF (none)
OFF (none)
OFF (disabled)
OFF
Settings
For RS-
For RS-
Description
232
422
communi
communi
cation
cation
0
0
1
2

7.2.11 Connecting to STARDOM

Make the communication settings as shown below.For
details of the communication settings, refer to the following
manual.
Peripheral Software Manual for YOKOGAWA
PLC
POINT
POINT
POINT
Connection between STARDOM and the PC for
communication settings
For the communication settings of STARDOM,
STARDOM and the PC for communication settings
must be connected to Ethernet using the Resource
Configurator (peripheral software).
COM port setting
Make the settings on the FCX Maintenance Page for
STARDOM.
1.
Select [Reboot (Maintenance Mode)] on the Reboot
screen of the FCX Maintenance Page to set the
maintenance mode.
2.
Set the COM1 port driver to be used.Execute [JEROS
Basic Setting File] from the [Edit System Setting File]
screen on the FCX Maintenance Page.
Confirm that the line of [Com1SioDriver] is as follows.
Com1SioDriver=DUONUS_SIO
3.
Set the COM1 port to be used.Execute [COM1 Port
Setting File] from the [Edit System Setting Files]
screen on the FCX Maintenance Page.Make the
settings as follows according to the communication
specifications on the setting screen.
Leave the settings as default if not listed on the
communication setting items.
(Communication setting items) ( ) in the table shows
the names on the FCX Maintenance Page.
Item
*1
Transmission speed (Baudrate)
*1
Data length (DataBitLength)
*1
Stop bit (StopBitLength)
*1
Parity bit (Parity)
Baudrate
DataBitLength
StopBitLength
Parity
FifoMode
InitialDTRState
SendFlowControlMode
ReceiveFlowControlMode
*1
Adjust the settings with GOT communication settings.
7.2.5 ■ Communication detail settings
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
Set value
4800bps, 9600bps,
19200bps, 38400bps,
57600bps, 115200bps
8bits, 7bits
1bit, 2bits
none/odd/even
= *1
= *1
= *1
= *1
= YES