Mitsubishi Electric GOT1000 Series Connection Manual page 202

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

4.
Select "Reboot (Online Mode)" on the "Reboot"
screen of the FCX Maintenance Page to set the online
mode.
Defining Logic POU
Define Logic POU using Logic Designer (peripheral
software), and download the project to STARDOM.
1.
Start Logic Designer and create a new project using a
template.
Use [STARDOM Serial Communication] template.
2.
Insert FA-M3 Emulator Firmware Library to the new
project.
(1) Right-click [Library] under the project tree in Logic
Designer.
(2) Right-click [Insert] and select [Firmware Library].
(3) Double-click the [SD_FCXPLCR_LIB] folder and
double-click [SD_FCXPLCR_LIB.fwl] to select it.
(4) The library path inserted in the procedures above
is as follows.
{Install Folder}\LogicDesigner\Mwt\Plc\Fw_lib\
SD_FCXPLCR_LIB\SD_FCXPLCR_LIB.fwl
3.
Insert FA-M3 Emulator User Library to the new
project.
(1) Right-click [Library] under the project tree in Logic
Designer.
(2) Right-click [Insert] and select [User Library].
(3) Double-click [SD_CFAM3R_PF.mwt] to select it.
(4) The library path inserted in the procedures above
is as follows.
{Install Folder}\LogicDesigner\Libraries\
SD_CFAM3R_PF.mwt
7 - 14
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
4.
Copy a sample project POU to the new project.
(1) Open C{Install Folder}\LogicDesigner\Projects\
EXAMPLE_J.mwt.
(2) Right-click [FAM3_Emulator] in the Logic POU
under the project tree in the Example_J project,
and select [Copy].
(3) Right-click the [Logic POU] under the project tree
in the created new project, and select [Paste].
(4) Double-click the [FAM3_Emulator*] file in the
[FAM3_Emulator*] folder.
(5) For the following terminals, set as shown below.
REQ terminal
TERMCHAR terminal : FALSE
PORT terminal
STATION terminal
SD_CFAM3R_OPEN_COM1
SD_CFAM3R_OPEN
(*VALID*)
TRUE
REQ
(*COM1*)
COM1
PORT
FALSE
TERMCHAR
FALSE
CHECKSUM
STATION
STATION1
I
I
D
D
B
B
COMERR1
COMERR
(Definition example of Logic POU)
5.
Defining the instance
Instantiate Logic POU. Define an already defined
instance to Task0.
(1) Right-click the [Physical hardware]
[Configuration:IPC_33/FCX01:FCX/Tasks/
Task0:CYCLIC] and select [Insert] - [Program
instance].
(2) Define the program instance name and select
FAM3_Emulator for the program type.
: TRUE
: COM1
: STATION1
VALID
VALID1
ERROR1
ERROR
STATUS1
STATUS
I
I
D
D
B
B
COMERR
COMERR1

Advertisement

Table of Contents
loading

Table of Contents