Connecting To S10Mini - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

3.2.2

Connecting to S10mini

Communication
S10mini
module
PLC
Communication
Series
*1
module
LQE560
LQE060
LQE160
S10mini
LQE565
LQE165
*1
Product manufactured by Hitachi, Ltd.For details of the product, contact Hitachi, Ltd.
*2
Connect it to the RS-232 interface (built into GOT). It cannot be mounted on GT1655 and GT155 .
3 - 4
3. CONNECTION TO HITACHI PLC
3.2 System Configuration
Connection cable
Connection cable
Commun
Cable model
ication
Connection diagram number
Type
GT09-C30R21301-9S (3m)
or
RS-232
RS232 connection diagram
1)
RS422 connection diagram
1)
GT09-C30R41301-9S (3m)
GT09-C100R41301-9S(10m)
RS-422
GT09-C200R41301-9S(20m)
GT09-C300R41301-9S(30m)
or
RS422 connection diagram
2)
GOT
GOT
Max.
Option device
distance
- (Built into GOT)
15m
GT15-RS2-9P
500m
- (Built into GOT)
GT16-C02R4-9S(0.2m)
*2
GT15-RS2T4-9P
500m
GT15-RS4-9S
- (Built into GOT)
Communication driver
HITACHI S10mini/S10V
Number of
connectable
Model
equipment
1 GOT for 1
communication
module