3.5 PLC Side Setting

POINT
POINT
POINT
HITACHI PLC
For details of HITACHI PLCs, refer to the following
manuals.
HITACHI PLC user's Manual
Model name
LQE560
LQE060
Communication module
LQE160
LQE565
LQE165
3 - 8
3. CONNECTION TO HITACHI PLC
3.5 PLC Side Setting
3.5.1
Communication settings
Make the communication settings of the
Communication module.
Refer to
Channel No. setting
Protocol setting
Transmission speed
3.5.1
Data bit
Parity bit
Start bit
Stop bit
Settings by switch
Make the communication settings using each setting
switch.
(1) Settings of the channel No. and the protocol
Switch position
Connecting to communication
module
Item
*1*2
#0 to #3
H-7338 protocol
19200bps (fixed)
8bits (fixed)
Odd (fixed)
1 bit (fixed)
1 bit (fixed)
*1
The ranges of available channel No. differ depending on the
model of communication module.
*2
Avoid duplication of the channel No.
Setting switches for the channel No.
and the protocol
CN1 MODU, CN2 MODU
Protocol
Channel No.
8
9
H-7338
A
B
Set value
0
CN1
#0
MODU
8
#1
0
#2
CN2
#3
MODU
8