Replacement of components

13.2.1 Replacement of fan
WARNING
The converter fan may be replaced only by properly qualified personnel.
The snubber capacitors continue to carry hazardous voltage for up to 2 minutes after isolation
from the supply. For this reason, the converter must not be opened for at least two minutes
after switch-off.
Non-observance of the safety instructions can result in death, severe personal injury or
substantial property damage.
Replacement of fan on D400 / 98 – 180 Mre converters
The two fans are mounted on the underside of the converter.
• Remove connector
• Release the two retaining clips
Installation:
• When mounting the fan make sure it is in the correct mounting position (blowing direction
upward, see arrow
• Insert the fan into lugs
• Insert connector
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
3
2
1
a
.
s
on the fan and swing fan out downwards.
d
on the fan housing).
f
and push upwards until it engages in retaining clips
a
again.
Maintenance
4
s
13-3