01.04
10.2
Alarm messages
Alarm message display:
On the PMU: A (Alarm) and a three-digit number. The red LED (Fault) flashes.
On the OP1S: On bottom line of operational display: The red LED (Fault) flashes.
An alarm message cannot be acknowledged, but disappears automatically when the cause has been
eliminated.
Several alarm messages can be active at the same time, these are then displayed in succession.
Many alarm messages can only occur in certain operating states.
(see list of alarm messages)
The system responses to an alarm are as follows:
Alarm message is displayed on the operator panel (PMU, OP1S)
B0114 ( = status word 1, bit 7) is set and B0115 is cancelled
(see also special alarm bits in status word 2, e.g. for an external alarm, overload, etc.)
The corresponding bit in one of the alarm words r953 (K9801) to r960 (K9808) is set
Alarm
A015
Simolink start
(active in all operating states)
Although the board has been initialized, it cannot yet exchange telegrams (parameters have not yet been correctly configured on
all nodes or the boards have not yet been linked via fiber optics to form a closed ring).
A018
Short circuit at binary outputs
(active in all operating states)
Hardware monitoring function to check for short circuit at one of the binary select outputs (see also F018 and r011).
A019
Alarm message from free function block FB256
(active in all operating states)
The binector wired via parameter U104 Index.002 is in the state log."1"
A020
Alarm message from free function block FB257
(active in all operating states)
The binector wired via parameter U105 Index.002 is in the state log."1"
A021
External alarm 1
(active in all operating states)
Bit 28 control word 2 was in the log. "0" state for longer than the time set in P360 index 003.
A022
External alarm 2
(active in all operating states)
Bit 29 in control word 2 was in the log. "0" state for longer than the time set in P360 index 004.
A023
Electrical stop / overtemperature
(active in all operating states)
The binector wired via parameter U104 Index.001 is in the state log."1". See crane control Section 8, Sheet K15
A024
Alarm message from free function block FB7
(active in all operating states)
The binector wired via parameter U105 Index.001 is in the state log."1"
A025
External fault 5
(active in all operating states ≤ o3 if P495=1)
A log. "0" signal has been on terminal 211 for more than 10s.
A026
External fault 6
(active in all operating states ≤ o6 if P496=1)
A log. "1" signal has been on terminal 212 for more than 2s.