7.6.15 Setting the rotor contactor stepping

Specifying limit values for switching over the rotor contactors (see Section 3.3.6 and 3.3.7):
On every control characteristic curve (in other words at a particular rotor resistance), the maximum
possible torque reduces as the speed increases. As a result, the converter switches to the next
rotor stage at the speed where the maximum possible torque is just 100% in order to receive an
appropriate acceleration torque (switchover points S2, S3 and S4 in Fig. 7.6.15.1)
see also Section 6.1 Block diagram
n
%
100
80
60
40
20
0
0
20
-20
-40
-60
-80
-100
Fig. 7.6.15.1
• with increasing speed:
U634 Value at which the rotor contactor for stage 2 is to be connected
U636 Value at which the rotor contactor for stage 3 is to be connected
U638 Value at which the rotor contactor for stage 4 is to be connected
• with decreasing speed:
U638 (– U639 hysteresis)
Value at which the rotor contactor for stage 4 is to be disconnected
U636 (– U637 hysteresis)
Value at which the rotor contactor for stage 3 is to be disconnected
U634 (– U635 hysteresis)
Value at which the rotor contactor for stage 2 is to be disconnected
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Full load curve
Lift
100
40
60
80
Full load curve
Lower
Rotor contactor switching cycle
Switch over to next
torque characteristic
Switchover point
S4
S3
S2
120
140
160
180
Mzus.
Switchover point S1a
(see Section 7.6.16)
Current limit
Activation of
rotor contactors:
Stage 4
Stage 3
Stage` 2
Stage 1
(Start-up stage)
%
M
Switchover point S1b
(see Section 7.6.16)
Y
Counter-torque stage
Start-up
7-17