01.04
Fault
Cause as a function of fault value
No.
(r047.001, r949.001 or r949.009 with acknowledged error)
F069
MLFB data are faulty
(active in all operating states)
Possible causes of fault
Excessive EMC-related interference
(e.g. due to unprotected contactors, unscreened cables, loose screen connections)
A7009 backplane wiring assembly is defective
Fault value:
1
MLFB code number (r070) = MLFB code number (r070)
is illegal
2
MLFB data checksum error
3
Works number checksum error
4
Number of words of MLFB data is incorrect
10.1.2.11 Communication errors with supplementary boards
F070
SCB1: Serious initialization error
(active in all operating states)
SCB1 and SCI cannot power up correctly (see diagnostic parameter n697 for details)
Fault value:
12
No connection to slave 1
22
No connection to slave 2
F073
SCB1: Current below 4mA minimum value at analog input1 of slave 1
(active in all operating states)
The cause of the fault may be a cable break
F074
SCB1: Current below 4mA minimum value at analog input2 of slave 1
(active in all operating states)
The cause of the fault may be a cable break
F075
SCB1: Current below 4mA minimum value at analog input3 of slave 1
(active in all operating states)
The cause of the fault may be a cable break
F076
SCB1: Current below 4mA minimum value at analog input1 of slave 2
(active in all operating states)
The cause of the fault may be a cable break
F077
SCB1: Current below 4mA minimum value at analog input2 of slave 2
(active in all operating states)
The cause of the fault may be a cable break
F078
SCB1: Current below 4mA minimum value at analog input3 of slave 2
(active in all operating states)
The cause of the fault may be a cable break
F079
SCB1: Telegram failure
(active in all operating states)
Check function of SCB1 (activity LEDs) and connection to SCI slaves (fiber optics)
F080
Error in initialization of a CB/TB board
Possible causes for fault values 1 and 6:
CB/TB board is defective
CB/TB board is not correctly inserted
CB/TB board is taking too long to run up (e.g. due to very complex TB board configuration)
Fault value:
1
The "Heartbeat counter" of the CB/TB has not started to
count within 20 s
2
The product version of the installed CT/TB board is not
compatible with the SIMOTRAS HD converter
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
i002 Incorrect MLFB code number
-
-
-
r047 Index 002 to 016:
i015 Code number of board:
st
1
TB or 1
nd
2
2
CB
i002 Code number of slot containing incompatible board:
2
Slot D
3
Slot E
4
Slot F
5
Slot G
6
CB when configuration includes TB
Faults / alarms