Siemens SIMOTRAS 6SG7050 Operating Instructions Manual page 353

6sg70 series
Table of Contents

Advertisement

01.04
PNU
Description
o8
Waiting for acknowledgement of starting lockout
o8.0
Waiting for acknowledgement of starting lockout through input
of SHUTDOWN command (OFF1).
o8.1
Reserved
o9
Fast stop (OFF3)
o9.0
Fast stop has been input via binector (acc. to selection in P658)
or control word, bit 2 (acc. to selection in P648).
o9.1
Fast stop has been input via binector (acc. to selection in
P659).
o9.2
Fast stop has been input via binector (acc. to selection in
P660).
o9.3
Fast stop is stored internally (memory can be reset by
cancelling FAST STOP command and entering SHUTDOWN).
o10
Voltage disconnection (OFF2)
o10.0 Voltage disconnection has been input via binector (acc. to
selection in P655) or control word, bit 1 (acc. to selection in
P648).
o10.1 Voltage disconnection has been input via binector (acc. to
selection in P656).
o10.2 Voltage disconnection has been input via binector (acc. to
selection in P657).
o10.3 Reserved
o10.4 Waiting for receipt of a valid telegram on G-SST1
(only if telegram failure time monitoring is set with P787 ≠ 0)
o10.5 Waiting for receipt of a valid telegram on G-SST2
(only if telegram failure time monitoring is set with P797 ≠ 0)
o10.6 Waiting for receipt of a valid telegram on G-SST3
(only if telegram failure time monitoring is set with P807 ≠ 0)
o11
Fault
o11.0 = Fxxx Fault message is displayed, red LED lights up.
o12
Electronics initialization in progress
o12.1 Basic converter electronics initialization in progress
o12.2 Initialization of supplementary board in location 2 progress
o12.3 Initialization of supplementary board in location 3 in progress
o12.9 Restructuring of parameters in non-volatile storage after
software update (takes approx. 15s)
o13
Software update in progress
o13.0 Waiting for arrival of start command from HEXLOAD PC routine
(press the DOWN key to abort this status and start a RESET)
o13.1 Deletion of Flash EPROM in progress
xxxxx
Display of address currently being programmed
o13.2 The Flash EPROM has been successfully programmed
(a RESET is performed automatically after approx. 1 second)
o13.3 Programming of the Flash EPROM has failed
(press UP key to return to operating state o13.0)
o14
Loading of boot sector in progress
(this operation is performed only in factory)
o15
Electronics not connected to voltage
Dark display:
Waiting for voltage at terminals 5U1, 5W1 (electronics supply
voltage).
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Value range
No. indices
[Unit]
Parameter list
See
Change
11-5