01.04
Temperature sensor inputs (see also Section 8, Sheet G185)
Function
Motor temperature
Connection of temperature sensor
Ground analog M
Analog outputs (see also Section 8, Sheet G115)
Function
Actual current
Ground analog M
Select output
analog 1
Ground analog M
Select output
analog 2
Ground analog M
Binary inputs (see also Section 8, Sheet G110)
Function
Supply for binary inputs
(output)
Ground digital M
Select input
binary 1
Power On / Shutdown
1 = power on
0 = shutdown
Enable operation
1 = enable controller
0 = disable controller
Select input
binary 2
Binary outputs (see also Section 8, Sheet G112)
Function
Select output
binary 1
Ground M
Select output
binary 2
Ground M
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Connection values/Remarks
Terminal
X174
22
Sensor acc. to P490 index 1
23
The cable to the temperature sensor on the motor must
be shielded and connected to ground at both ends.
24
Connection values/Remarks
Terminal
X175
12
0 . . . ±10V corresponds to 0 . . . ±200%
13
Converter rated current
Max. load 2mA, short-circuit-proof
14
0 . . . ±10V, max. 2mA
short-circuit proof
15
16
Resolution ±11bit
17
Connection values/Remarks
Terminal
X171
34
24V DC, short circuit proof
max. load 200mA (terminals 34, 44, and 210 combined),
internal supply with respect to internal ground
35
Overload response: Error signal F018
36
H signal: +13V to +33V
L signal: – 33V to +3V or terminal open
37
8.5mA at 24V
38
39
Terminal
Connection values/Remarks
X171
46
H signal: +20V to +26V
L signal: 0 to +2V
47
Short-circuit-proof 100mA
48
Internal snubber circuit (free-wheeling diode)
54
Overload response: Error signal F018
Warning signal A018
Warning signal A018