List of connectors and binectors
12.1

Connector list

Display:
The values of connectors can be displayed via parameters r041, r042, r043 and P044.
Normalization: The following applies unless stated otherwise:
100% corresponds
for currents, to the converter rated current (r072.i002),
for voltages, to the converter rated voltage (P078.i001)
or, for speeds, to the parameterized maximum speed (P741 or P143).
Numeric representation:
100% corresponds to the figure of 4000 hex = 16384 dec
The displayable value range is -200.00% to +199.99%, corresponding to 8000 hex ... 7FFF hex.
The connectors are transferred in this numerical format via the serial interfaces.
Connector
Description
Fixed values
Fixed value 0
K0000
K0001
Fixed value 100.00%
Fixed value 200.00%
K0002
K0003
Fixed value -100.00%
K0004
Fixed value -200.00%
Fixed value 50.00%
K0005
K0006
Fixed value 150.00%
Fixed value -50.00%
K0007
K0008
Fixed value -150.00%
K0009
Fixed value 0 or special function specified in each case
Analog inputs
Analog input, terminal 4 / 5 (main setpoint)
K0010
Raw value after A/D conversion (unfiltered, not normalized)
K0011
Analog input, terminal 4 / 5 (main setpoint)
After normalization, offset injection, filtering
K0012
Analog input, terminal 103 / 104 (main actual value)
Raw value after A/D conversion (unfiltered, not normalized)
Analog input, terminal 103 / 104 (main actual value)
K0013
After normalization, offset injection, filtering
K0014
Analog input, terminal 6 / 7 (analog selectable input 1)
Raw value after A/D conversion (unfiltered, not normalized)
K0015
Analog input, terminal 6 / 7 (analog selectable input 1)
After normalization, offset injection, filtering
Analog input, terminal 8 / 9 (analog selectable input 2)
K0016
Raw value after A/D conversion (unfiltered, not normalized)
Analog input, terminal 8 / 9 (analog selectable input 2)
K0017
After normalization, offset injection, filtering
K0018
Analog input, terminal 10 / 11 (analog selectable input 3)
Raw value after A/D conversion (unfiltered, not normalized)
Analog input, terminal 10 / 11 (analog selectable input 3)
K0019
After normalization, offset injection, filtering
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Connectors and binectors
Normalization
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
Function
diag., Sheet
G120
G120
G120
G120
G120
G120
G120
G120
G120
G113
G113
G113
G113
G113
G113
G114
G114
G114
G114
12-1