Procedure For Updating Software (Upgrading To A New Software Version) - Siemens SIMOTRAS 6SG7050 Operating Instructions Manual

6sg70 series
Table of Contents

Advertisement

Maintenance
13.1
Procedure for updating software
(upgrading to a new software version)
Read out and write down all parameter
1
contents.
(also note software version in r060.001 and
r065.001!)
Switch off electronics power supply
2
Connect one COM port on the PC to
3
connector X300 on the converter
Switch on electronics power supply AND press
4
down the UP key on the PMU of the
SIMOTRAS HD converter at the same time
⇒ The SIMOTRAS HD converter switches to
operating state o13.0
Open a DOS window on the PC and enter
5
program call:
HEXLOAD 7001Axxx.H86 7001Bxxx.H86 COMx
Start the program by pressing Return
⇒ The software update is performed
automatically
⇒ When the software has been updated
6
successfully, the SIMOTRAS HD switches
to operating state o13.2 for approx. 1 s
⇒ The SIMOTRAS HD converter then
switches to operating state o12.9 in many
cases (depending on which SW version
was previously installed in the converter)
for approximately 15s.
Check the checksum:
7
Comparison of the value of parameter r062.001 with the checksum in the Internet under menu item
"Info" (see the inside page of the cover sheet of the operation instructions).
Was the electronics supply disconnected while
8
Step 6 was in progress?
12
13-2
n
o
Note:
The parameter set can be transferred to a PC or
programming device by means of DriveMonitor
(see also Section 15).
Cable order number: 6SX7005-0AB00
(see also Section 15.3)
Note:
A software update can be started only from the
PMU panel and not via an OP1S or the
DriveMonitor system
Note:
HEXLOAD.EXE:
Loading program
7001Axxx.H86 and 7001Bxxx.H86:
Data files which contain the SIMOTRAS software
xxx is the SW release
COMx: COM1 or COM2
Note:
The currently programmed addressed is displayed
on the PMU while the update is in progress
The current status of the update routine is
displayed on the PC
yes
?
Acknowledge any fault message that may
9b
appear on the SIMOTRAS HD device
Restore default setting
10b
(see Section 7.4)
Start up the converter again
11b
(see Section 7.5)
Note:
The parameter set stored in Step 1 above can
be loaded from a PC or programming device
by means of DriveMonitor.
End