Faults / alarms
Fault
Cause as a function of fault value
No.
(r047.001, r949.001 or r949.009 with acknowledged error)
10.1.2.8 External faults
F053
Fault message from free function block FB288
(active in all operating states)
Fault value:
1
the binector wired via parameter U102 Index.005 is in the state log."1"
2
the binector wired via parameter U102 Index.006 is in the state log."1"
3
the binector wired via parameter U102 Index.007 is in the state log."1"
4
the binector wired via parameter U102 Index.008 is in the state log."1"
F054
Fault message from free function block FB289
(active in all operating states)
Fault value:
1
the binector wired via parameter U103 Index.005 is in the state log."1"
2
the binector wired via parameter U103 Index.006 is in the state log."1"
3
the binector wired via parameter U103 Index.007 is in the state log."1"
4
the binector wired via parameter U103 Index.008 is in the state log."1"
10.1.2.9 Start-up faults
F056
Important parameter is not set
(active in operating states of ≤ o6)
This fault message is activated if certain parameters are still set to 0.
Fault value:
1
Speed controller actual value selection in P083 is still set to 0
2
Rated motor current in P100 is still set to 0.0
F058
Parameter settings are not consistent
(active in operating states of ≤ o6)
Inconsistent values have been set in mutually dependent parameters.
Fault value:
4
The first threshold for P gain adaptation of the speed controller set in parameter P556 is higher than the second threshold
setting in parameter P559
5
P557 is set to greater than P560
6
P558 is set to greater than P561
7
If P083=1 (analog tachometer), then P746 may not equal 0 (main actual value is not connected)
8
If P083=2 (pulse encoder), then P140 may not equal x0 (no pulse encoder installed)
10
P090 (stabilization time for supply voltage) >P086 (time for automatic restart)
11
P090 (stabilization time for supply voltage) >P089 (waiting time in state o4 or o5)
12
P445=1 is set (switch-on, shutdown and crawl act as a pushbutton) although no binector is parameterized as a shutdown
button (P444=0)
14
Parameter U673 > U674 (this setting is not permitted; see function diagram B152)
10-10
Description
Further information (r047.002 to r047.016)