Parameter list
PNU
Description
U756
Normalization of analog inputs on EB1
(2756)
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
(Z112)
The following general rule applies:
(Z115)
With a voltage input:
[%] =
U
756
10
With a current input:
[%] =
U
756
20
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U757
Offset for analog inputs on EB1
(2757)
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
(Z112)
i004: AI1 of the second EB1
(Z115)
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U758
Mode of signal injection at analog inputs on EB1
(2758)
0 = Injection of signal with sign
1 = Injection of absolute value of signal
*
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
(Z112)
(Z115)
i001: AI1 of the first EB2
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB2
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U759
Source for selecting sign reversal of analog inputs on EB1
(2759)
Selection of binector to control sign reversal at the analog input ("1" state
= reverse sign)
*
0 = binector B0000
1 = binector B0001
(Z112)
etc.
(Z115)
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U760
Filtering time for analog inputs on EB1
(2760)
Note: Hardware filtering of approximately 0.2 ms is applied as standard
*
i001: AI1 of the first EB1
i002: AI2 of the first EB1
(Z112)
i003: AI3 of the first EB1
(Z115)
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
11-144
Y
X .. Input voltage in volts
V
X
Y .. % value which is generated for input
current X
Y
X .. Input current in mA
mA
X
Y .. % value which is generated for input
current X
Value range
No. indices
[Unit]
-1000.0 to 1000.0
Ind: 6
[%]
FS=100.0
0.1%
Type: I2
-100.00 to 100.00
Ind: 6
[%]
FS=0.00
0.01%
Type: I2
0 to 3
Ind: 6
1
FS=0
Type: O2
All binector numbers
Ind: 6
1
FS=0
Type: L2
0 to 10000
Ind: 6
[ms]
FS=0
1ms
Type: O2
SIEMENS AG
SIMOTRAS HD
Operating Instructions
01.04
See
Change
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
6SG7000-0BA76