Binector List - Siemens SIMOTRAS 6SG7050 Operating Instructions Manual

6sg70 series
Table of Contents

Advertisement

Connectors and binectors
12.2

Binector list

The states of binectors can be displayed via parameters r045 and P046.
Binector
Name, description
Fixed values
B0000
Fixed value 0
Fixed value 1
B0001
Binary inputs, terminals 36 to 43
B0010
Status of terminal 36
Status of terminal 36, inverted
B0011
B0012
Status of terminal 37
Status of terminal 37, inverted
B0013
B0014
Status of terminal 38
Status of terminal 38, inverted
B0015
B0016
Status of terminal 39
Status of terminal 39, inverted
B0017
B0018
Status of terminal 40
B0019
Status of terminal 40, inverted
B0020
Status of terminal 41
B0021
Status of terminal 41, inverted
Status of terminal 42
B0022
B0023
Status of terminal 42, inverted
Status of terminal 43
B0024
B0025
Status of terminal 43, inverted
Binary inputs, terminals 211 to 214
Status of terminal 211
B0040
B0041
Status of terminal 211, inverted
Status of terminal 212
B0042
B0043
Status of terminal 212, inverted
Status of terminal 213
B0044
B0045
Status of terminal 213, inverted
Status of terminal 214
B0046
B0047
Status of terminal 214, inverted
Analog inputs
Analog input, terminal 4: 1 = Open circuit (i ≤ 2 mA)
B0050
Analog input, terminal 6: 1 = Open circuit (i ≤ 2 mA)
B0051
Pulse encoder evaluation
Fault in digital speed sensing circuit
B0052
B0053
Underflow of actual position value
This binector changes to 1 when connector KK0046 (actual position value extended in software to a 32-bit
value) counts from value 8000 0000H (= –2
Binector B0053 does not change back to 0 until connector KK0046 assumes a value other than 7FFF
31
FFFFH (= +2
Overrflow of actual position value
B0054
This binector changes to 1 when connector KK0046 (actual position value extended in software to a 32-bit
value) counts from value 7FFF FFFFH (= +2
Binector B0054 does not change back to 0 until connector KK0046 assumes a value other than 8000
31
0000H (= –2
12-24
–1) again.
) again.
31
) to value 7FFF FFFFH (= +2
31
–1) to value 8000 0000H (= –2
[SW 1.9 and later]
31
–1).
[SW 1.9 and later]
31
).
SIEMENS AG
SIMOTRAS HD
Operating Instructions
01.04
Function
diag., Sheet
G120
G120
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G110
G186
G186
G186
G186
G186
G186
G186
G186
G113
G113
G145
G145
G145
6SG7000-0BA76

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents