01.04
PNU
Description
U807
Telegram failure time on paralleling interface
(2807)
0
0.001...65.000 Permissible time interval between two data exchange
(G195)
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
U808
Source for triggering of message F014
(2808)
Selection of binector which must trigger message F014 when it switches to
*
log. "1"
(G195)
6040 = binector B6040
6041 = binector B6041
n809
Diagnostic information for paralleling interface
(2809)
i001 to i009 = Free-running counter, overflow at 65535
(G195)
i001:
Number of error-free telegrams
i002:
Number of errored telegrams
i003:
Transmit Error Counter
i004:
Receive Error Counter
i005:
Phase Error Counter
i006:
Baud rate Error Counter
i007:
Bad BCC Counter
i008:
Timeout Counter
i009:
Number of telegrams with unknown identifier
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
No time monitoring
operations before a fault message is output.
Value range
[Unit]
0.000 to 65.000
[SW 2.1 and later]
[s]
0.001s
6040, 6041
[SW 2.1 and later]
[SW 2.1 and later]
0 to 65535
Parameter list
No. indices
See
Change
Ind: None
P052 = 3
FS=0.100
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=6040
P051 = 40
Type: L2
Offline
P052 ≥ 0
Ind: 9
Type: O2
11-151