4.4

Activating / deactivating individual drive components

Function description
Configure the drive, which comprises a CU and additional components, in the device view
(DRIVE-CLiQ Editor). All drive components are activated by default.
When replacing parts, carrying out testing or service, it may be necessary to briefly deactivate
and then reactivate individual components. The following options are available in the device
view:
• Deactivate component:
Deactivates a selected component.
• Activate component:
Activates a deactivated component.
• Deactivate component and not available:
Deactivates individual components in a large drive line-up that are actually missing. This
facilitates the maximum expansion level of a drive project.
Deactivated components in the drive project can also be missing in the hardware without any
errors being generated because of it. Possible applications are, for example, testing parts of
a large plant or commissioning components when parts are replaced.
Components that can be deactivated:
The components that can be deactivated are listed in the following table:
Component
Control Unit (CU)
Line Module
Power Module
Motor Module
Motor
Measuring systems / encoders
Encoder evaluation
Control Unit Adapter (CUA)
DRIVE CLiQ Hub Module (DMC20 / DME20)
Communication Board (CBE 20)
Terminal Board (TB30)
Terminal Modules
Voltage Sensing Modules
The following applies to individual components and not to drive objects.
1)
Only available for CU320-2 PN.
2)
For CU310-2 PN, the Control Unit Adapter (CUA) is not available for PM240-2.
3)
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
2)
3)
2)
2)
2)
4.4 Activating / deactivating individual drive components
All/no options can be used