01.04
PNU
Description
U749
SLB Read address
(2749)
Definition of node addresses and channels from which the SLB must read
data (a total of 8 channels can be read according to the index entries). The
*
digits before the decimal point in the input value define the node address
and those after the point the channel number (see also Section 7 "Starting
up SIMOLINK boards" and Section 8 Sheet Z122).
Example:
2.0 = address 2 channel 0
n750
SLB Receive data
(2750)
Visualization parameter for data received via the SIMOLINK board (see
also Section 7 "Starting up SIMOLINK boards" and Section 8 Sheet Z122)
(Z122)
i001: Word 1 PZD section of telegram
...
i016: Word 16 in PZD section of telegram
U751
SLB Transmit data selection
(2751)
Selection of connectors whose contents must be transferred as transmit
data by the SLB (see also Section 7 "Starting up SIMOLINK boards" and
*
Section 8 Sheet Z122).
0 = connector K0000
(Z122)
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001: Channel0, low word
i002: Channel0, high word
...
i015: Channel7, low word
i016: Channel7, high word
n752
SLB Display of transmit data
(2752)
Process data transmitted by SLB via SIMOLINK in hexadecimal notation
(see also Section 7 "Starting up SIMOLINK boards" and Section 8 Sheet
(Z122)
Z122)
U753
SLB Fault delay
(2753)
Delay in activation of fault message F015 (see also U741)
*
0 = fault message is activated immediately the telegram failure monitor
(Z121)
responds
11.80 Configuring the EB1 expansion boards
U755
Signal type of analog inputs on EB1
(2755)
0 = voltage input 0 to ± 10 V
1 = current input 0 to ± 20 mA
*
(Z112)
i001: AI1 of the first EB2
(Z115)
i002: AI1 of the second EB2
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Value range
No. indices
[Unit]
0.0 to 200.7
Ind: 8
0.1
FS=0.0
Type: O2
Ind: 16
Type: L2
All connector
Ind: 16
numbers
FS=0
Type: L2
Ind: 16
Type: L2
0.0 to 100.0
Ind: None
[s]
FS=0.0
0.1
Type: O2
0 to 1
Ind: 2
1
FS=0
Type: O2
Parameter list
See
Change
P052 = 3
P051 = 40
Offline
P052 = 3
P052 = 3
P051 = 40
Offline
P052 = 3
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
11-143