Siemens SIMOTRAS 6SG7050 Operating Instructions Manual page 84

6sg70 series
Table of Contents

Advertisement

Connections
Control outputs (electrically isolated relay outputs) (see also Section 8, Sheets G112 and G119)
Function
Control output
In the factory setting, the parameter is
wired as the output "No fault"
Control output
In the factory setting, the parameter is
wired as the output "No fault"
Function
Control output
In the factory setting, the parameter is
wired as the output "Acknowledgement"
Control output
In the factory setting, the parameter is
wired as the output "Brake contactor"
Function
S1 - "Rotor contactor stage 1"
Relay signal
"Switch rotor contactor S1"
S2 - "Rotor contactor stage 2"
Relay signal
"Switch rotor contactor S2"
Function
S3 - "Rotor contactor stage 3"
Relay signal
"Switch rotor contactor S3"
S4 - "Rotor contactor stage 4"
Relay signal
"Switch rotor contactor S4"
6-38
Connection values/Remarks
Terminal
LED
X2_4
109
H109
Load capability:
110
= 250V AC, 4A; cos Φ =1
= 250V AC, 2A; cos Φ =0,4
= 30V DC, 2A
81
H81
82
Connection values/Remarks
Terminal
LED
X2_3
83
H83
Load capability:
84
= 250V AC, 4A; cos Φ =1
= 250V AC, 2A; cos Φ =0,4
= 30V DC, 2A
85
H85
86
Connection values/Remarks
Terminal
LED
X2_2
87
H87
Load capability:
88
= 250V AC, 4A; cos Φ =1
= 250V AC, 2A; cos Φ =0,4
= 30V DC, 2A
89
H89
90
Connection values/Remarks
Terminal
LED
X2_1
91
H91
Load capability:
92
= 250V AC, 4A; cos Φ =1
= 250V AC, 2A; cos Φ =0,4
= 30V DC, 2A
93
H93
94
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
01.04

Hide quick links:

Advertisement

Table of Contents
loading