Siemens SIMOTRAS 6SG7050 Operating Instructions Manual page 411

6sg70 series
Table of Contents

Advertisement

01.04
PNU
Description
P787
Telegram failure time for G-SST1
The failure time set in this parameter is valid when setting P780=2 (USS
(G170)
protocol) is selected.
0.000
0.001...65.000 Time which may elapse between the receipt of two
Fault message F011 is activated if no valid telegram is received within this
time period.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
P788
Source for triggering of message F011
*
Selection of binector which must trigger message F011 when it switches to
(G170)
log. "1"
2030 = binector B2030
2031 = binector B2031
r789
Diagnostic information for G-SST1
Free-running counter, overflow at 65535
(G170)
i001:
Number of error-free telegrams
i002:
Number of errored telegrams:
Byte frame, parity, overrun or BCC error
i003:
Number of byte frame errors
i004:
Number of overrun errors
i005:
Parity error
i006:
STX error:
Start interval before STX not observed,
telegram residual transfer time not observed,
delay time of LGE character too long,
erroneous STX, i.e. ≠ 02
i007:
Violation of telegram residual transfer time
i008:
Block check error
i009:
Incorrect telegram length:
With P782=3 or 4 only:
The length of the received telegram is ≠ P781 + P782
(Note: If the received values are correct, they will be processed
even when this error has been detected)
i010:
Timeout error:
No valid telegram has been received for a period exceeding the
setting in P787. After the occurrence of a timeout error, this
counter is not activated again until the next valid telegram is
received.
G-SST 2 (RS485 on X172) (see also Section 8, Sheets G171 and G173 and Section 9)
P790
Selection of protocol for G-SST2 basic converter interface
*
0
Setting has no function
(G171)
2
USS protocol
(G173)
5
"Peer-to-peer" communication
9
For internal factory test purposes
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
No time monitoring
telegrams addressed to the unit before a fault message
is activated.
Value range
No. indices
[Unit]
0.000 to 65.000
Ind: None
[s]
FS=0.000
0.001s
Type: O2
2030, 2031
Ind: None
FS=2030
Type: L2
Ind: 10
Type: O2
0, 2, 5, 9
Ind: None
1
FS=0
Type: O2
Parameter list
See
Change
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P052 = 3
P051 = 40
Offline
11-63