Siemens SIMOTRAS 6SG7050 Operating Instructions Manual page 384

6sg70 series
Table of Contents

Advertisement

Parameter list
PNU
Description
P468
Setpoint for "Raise motorized potentiometer"
FDS
Motorized potentiometer manual operation: Setpoint for "Raise motorized
(G126)
potentiometer"
P469
Setpoint for "Lower motorized potentiometer"
FDS
Motorized potentiometer manual operation: Setpoint for "Lower motorized
(G126)
potentiometer"
P470
Source for clockwise/counter-clockwise switchover
*
Selection of binector to control "Clockwise/counter-clockwise
BDS
switchover" ("0" state = clockwise).
0 = binector B0000
(G126)
1 = binector B0001
etc.
P471
Source for manual/automatic switchover
*
Selection of binector to control "Manual/automatic switchover"
BDS
("0" state = manual).
(G126)
0 = binector B0000
1 = binector B0001
etc.
P472
Source for set motorized potentiometer
*
Selection of binector to control "Set motorized potentiometer"
BDS
("0" to "1" transition = set motorized potentiometer).
0 = binector B0000
(G126)
1 = binector B0001
etc.
P473
Storage of output value
*
0
No storage of output value:
FDS
The output is set to 0 in all operating states of >o5.
The starting point after ON is determined by P467 (MOP
(G126)
starting value).
1
Non-volatile storage of output value:
The output value remains stored in all operating states and after
voltage disconnection or failure. The last value stored is output
again after voltage recovery/reconnection.
11.23 Oscillation
Function:
Parameters P480 to P483 define the waveshape of a rectangular signal (oscillation setpoint K0203). The value set in P480 determines
the signal level for the time period set in P481 and the value set in P482 the signal level for the time period set in P483.
Oscillation: Selected in P485. The free-running rectangular signal is switched through to the output K0208.
P480
Oscillation setpoint 1
FDS
(G128)
P481
Oscillation time 1
FDS
(G128)
P482
Oscillation setpoint 2
FDS
(G128)
P483
Oscillation time 2
FDS
(G128)
P484
Source for standard setpoint
*
Selection of connector to be injected as the output value when the
FDS
"Oscillation" function is not selected
(G128)
0 = connector K0000
1 = connector K0001
etc.
11-36
Value range
No. indices
[Unit]
-199.99 to 199.99
Ind: 4
[%]
FS=100.00
0.01%
Type: I2
-199.99 to 199.99
Ind: 4
[%]
FS=-100.00
0.01%
Type: I2
All binector numbers
Ind: 2
1
FS=0
Type: L2
All binector numbers
Ind: 2
1
FS=0
Type: L2
All binector numbers
Ind: 2
1
FS=0
Type: L2
0 to 1
Ind: 4
1
FS=0
Type: O2
-199.9 to 199.9
Ind: 4
[%]
FS=5.0
0.1% of maximum
Type: I2
speed
0.1 to 300.0
Ind: 4
[s]
FS=2.0
0.1s
Type: O2
-199.9 to 199.9
Ind: 4
[%]
FS=-0.0
0.1% of maximum
Type: I2
speed
0.1 to 300.0
Ind: 4
[s]
FS=2.0
0.1s
Type: O2
All connector
Ind: 4
numbers
FS=209
1
Type: L2
SIEMENS AG
SIMOTRAS HD
Operating Instructions
01.04
See
Change
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
6SG7000-0BA76