Siemens SIMOTRAS 6SG7050 Operating Instructions Manual page 129

6sg70 series
Table of Contents

Advertisement

01.04
Diagnostic parameter n732:
Indices i001 to i032 apply to a CBC as the first communication board; indices i033 to i064 apply to a
CBC as the second communication board.
n732.001
or
n732.033
n732.002
or
n732.034
n732.003
or
n732.035
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
Value
0
No fault
Fault F080/fault value 5 is displayed under fault conditions:
Fault values for CAN layer 2:
1
Incorrect address on CAN Bus (P918 / slave address)
2
Incorrect CAN identifier with PKW Request (U711)
5
Incorrect CAN identifier with PKW Request-Broadcast (U719)
7
Incorrect CAN identifier with PZD Receive (U712)
13
Incorrect CAN identifier with PZD Transmit (U713)
14
PZD transmit length = 0 (U714)
15
PZD transmit length > 16 , i.e. too long (U714)
20
Incorrect CAN identifier with PZD Receive-Broadcast (U716)
21
Incorrect CAN identifier with PZD Receive-Multicast (U717)
22
Incorrect CAN identifier with PZD Receive-Internode (U718)
23
Invalid baud rate (U720)
35
Incorrect CAN protocol type (U721)
36
PKW Request-Broadcast (U719) without PKW Request (U711)
48
Overlap between CAN identifier PKW and PKW Broadcast
49
Overlap between CAN identifier PKW and PZD Receive
50
Overlap between CAN identifier PKW and PZD Transmit
51
Overlap between CAN identifier PKW and PZD Receive-Broadcast
52
Overlap between CAN identifier PKW and PZD Receive-Multicast
53
Overlap between CAN identifier PKW and PZD Receive-Internode
54
Overlap between CAN identifier PKW Broadcast and PZD Receive
55
Overlap between CAN identifier PKW Broadcast and PZD Transmit
56
Overlap between CAN identifier PKW Broadcast and PZD Receive-Broadcast
57
Overlap between CAN identifier PKW Broadcast and PZD Receive-Multicast
58
Overlap between CAN identifier PKW Broadcast and PZD Receive-Internode
59
Overlap between CAN identifier PZD Receive and PZD Transmit
60
Overlap between CAN identifier PZD Receive and PZD Receive-Broadcast
61
Overlap between CAN identifier PZD Receive and PZD Receive-Multicast
62
Overlap between CAN identifier PZD Receive and PZD Receive-Internode
63
Overlap between CAN identifier PZD Transmit and PZD Receive-Broadcast
64
Overlap between CAN identifier PZD Transmit and PZD Receive-Multicast
65
Overlap between CAN identifier PZD Transmit and PZD Receive Internode
66
Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Multicast
67
Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Internode
68
Overlap between CAN identifier PZD Receive-Multicast and PZD Receive-Internode
Fault values for CANopen:
1
Incorrect bus address (P918)
23
Invalid baud rate (U720)
35
Incorrect CAN protocol type (U721)
257
Invalid mapping of 1st Receive PDO (U711)
258
Invalid transmission type of 1
273
Invalid mapping of 1
Invalid transmission type of 1
274
513
Invalid mapping of 2
514
Invalid transmission type of 2
529
Invalid mapping of 2
530
Invalid transmission type of 2
769
Invalid mapping of 3
770
Invalid transmission type of 3
785
Invalid mapping of 3
786
Invalid transmission type of 3
1025
Invalid mapping of 4
1026
Invalid transmission type of 4
1041
Invalid mapping of 4
1042
Invalid transmission type of 4
1092
Invalid Life Time Event or incorrect basic unit parameterized (U719)
Number of correctly received PZD CAN telegrams since Power ON
Irrelevant for CANopen
Number of PZD telegrams lost since Power ON
Telegrams will be lost if the CAN Bus master sends PZD telegrams faster than they can
be processed by the slave.
Irrelevant for CANopen
Meaning
st
Receive PDO (U711)
st
Transmit PDO (U715)
st
Transmit PDO (U715)
nd
Receive PDO (U712)
nd
Receive PDO (U712)
nd
Transmit PDO (U716)
nd
Transmit PDO (U716)
rd
Receive PDO (U713)
rd
Receive PDO (U713)
rd
Transmit PDO (U717)
rd
Transmit PDO (U717)
th
Receive PDO (U714)
th
Receive PDO (U714)
th
Transmit PDO (U718)
th
Transmit PDO (U718)
Start-up
7-43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents