Starting up optional supplementary boards

For information about installing boards, please see Section 5.2.2, Optional supplementary boards.
This section also contains details on the number of supplementary boards that can be installed and
in which slots they may be inserted.
The basic converter automatically detects all installed supplementary boards during power-up.
All communications-related settings must be made by means of parameters. The function diagrams
in Section 8 show a general overview of the parameters provided for this purpose.
If two boards of the same type (e.g. two EB1s) are installed in a converter, the slots in which they
are installed determine the parameter settings. The board in the slot with the lower slot letter is the
st
1
board (e.g. the 1
nd
(e.g. 2
EB1).
st
The 1
board is parameterized via index 1 and the 2
parameter (e.g. to define the signal type of the analog inputs of boards of type EB1, parameter
U755.001 is used for the 1

7.10.1 Sequence of operations for starting up the T300 technology board

NOTE
Freely configurable technology boards T300 are guaranteed to operate correctly (board runup and
data exchange with the SIMOTRAS 6SG70). The user, however, must bear responsibility for
ensuring that the system is properly configured.
Disconnect the power supply and insert the board in location 2.
1
Power up the system again to gain access to the parameters of the technology board (d and
2
H parameters, as well as c and L parameters if programmed).
The process data are interconnected at the basic converter end by means of the appropriate
connectors and binectors (see Section 8, function diagram Z110)
For meaning of bits of control and status words, please see Section 8, Sheets G180 to G183.
If a communication board is used in addition to a technology board, then data are exchanged
with the basic converter via the technology board. The basic converter cannot directly access
the data of the communication board. The connections of the transfer data are then
determined by the configuration or parameter settings of the technology board.
If a technology board is mounted in location 2, then only one communication board (CBP2,
CBC, ...) may be installed in slot G. Other boards are not supported.
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
st
EB1) of this particular type and the board with the higher letter the 2
st
EB1 and parameter U755.002 for the 2
nd
board via index 2 of the corresponding
nd
EB1).
Start-up
nd
board
7-27