Connections
Analog inputs (see also Section 8, Sheet G114)
Function
Select input
analog 2
Ground analog
Select input
analog 3
Ground analog
Analog outputs, temperature sensor input (see also Section 8, Sheets G116 and G185)
Function
Select output
analog 3
Ground analog M
Select output
analog 4
Ground analog M
Temperature sensor input
Serial interface 3 (G-SST3) RS485
Function
Terminal
TX+
TX-
RX+/TX+
RX-/TX-
M
For transmission rate =187.5kBd ⇒ 600m
Cable length:
For transmission rate = 93.75kBd ⇒ 1200m
The following must be observed: DIN 19245 Part 1
The potential difference between the data reference potentials M of all interfaces must not
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be
provided.
Activate interface 3:
– Set the baud rate in parameter P803.
– Set the protocol in parameter P800.
6-40
Terminal
X164
8
9
10
11
Terminal
X164
18
19
20
21
204
205
Connection values/Remarks
X162
61
RS485, 4-wire send cable, positive differential input
62
RS485, 4-wire send cable, negative differential input
63
RS485, 4-wire receive cable, positive differential input,
2-wire send/receive cable, positive differential input
64
RS485, 4-wire receive cable, negative differential input,
2-wire send/receive cable, negative differential input
65
Ground
Connection values/Remarks
±10V, 52k Ω
Resolution: ±10bit
Common mode suppression: ±15V
Connection values/Remarks
0 . . . ±10V, max. 2mA
short-circuit proof
Resolution ±11bit
Sensor acc. to P490 Index 2
The cable to the temperature sensor on the motor must
be shielded and connected to ground at both ends.
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
01.04