Parameter list
PNU
Description
P321
Multiplier for additional setpoint
FDS
(G135)
P322
Source for multiplier for main setpoint
*
0 = connector K0000
FDS
1 = connector K0001
(G135)
etc.
P323
Source for multiplier for additional setpoint
*
0 = connector K0000
FDS
1 = connector K0001
(G135)
etc.
11.14 Ramp-function generator
P330
Factor for ramp-function generator times
*
Selection of a factor for the values set in parameters P296, P297, P298,
FDS
P303 to P314 and P542 (ramp-function generator times).
(G136)
0
Factor = 1
1
Factor = 60
i.e. effective ramp-function generator times = values set in
[minutes] instead of in [seconds]
11.15 Setting values for monitoring functions and limits
Setting values for monitoring functions
P351
Threshold for undervoltage trip
If the line voltage exceeds a specific value and does not return to the
FDS
permissible tolerance range within the "Restart time" set in P086, fault
message F006 is activated. The drive dwells in operating state o4 while the
line undervoltage persists.
P352
Source for overvoltage trip
If the line voltage exceeds a specific value and does not return to the
FDS
permissible tolerance range within the "Restart time" set in P086, fault
message F007 is activated.
P353
Response threshold for phase failure monitoring
If the line voltage drops below the permissible value in operating states of
FDS
≤ o4 and does not return to an "acceptable" value within the "Restart time"
set in P086, fault message F004 is activated.
The drive dwells in operating state o4 for the period that the line voltage
remains below the threshold and during the subsequent voltage
stabilization period set in P090.
When a switch-on command is entered, the converter dwells in operating
state o4 for a maximum delay period set in P089 until the voltages in all
phases exceed the threshold set in this parameter before fault message
F004 is activated.
P355
Stall protection time
F035 is activated if the conditions for the "Stall protection" fault message
FDS
are fulfilled for longer than the period set in P355.
When P355=0.0, the "Drive blocked" monitoring function (F035) is
deactivated and alarm A035 is likewise suppressed.
P360
Response delay for external faults and alarms
The fault message or alarm is not activated on the converter until the
(G180)
appropriate input or corresponding control word bit (as selected in P675,
(G181)
P686, P688 or P689) has been in the LOW state for at least the time period
set in this parameter (see also Section 8, Sheets G180 and G181).
i001:
Delay for external fault 1
i002:
Delay for external fault 2
i003:
Delay for external alarm 1
i004:
Delay for external alarm 2
11-28
Value range
[Unit]
-300.00 to 300.00
[%]
0.01%
All connector
numbers
1
All connector
numbers
1
[SW 2.1 and later]
0 to 1
1
-90 to 0
[%]
1% of P078.001
0 to 99
[%]
1% of P078.001
10 to 100
[%]
1% of P078.001
0.0 to 600.0
[s]
0.1s
0 to 10000
[ms]
1ms
No. indices
Ind: 4
FS=100.00
Type: I2
Ind: 4
FS=1
Type: L2
Ind: 4
FS=1
Type: L2
Ind: 4
FS=0
Type: O2
Ind: 4
FS=-80
Type: I2
Ind: 4
FS=40
Type: O2
Ind: 4
FS=20
Type: O2
Ind: 4
FS=0.5
Type: O2
Ind: 4
FS=0
Type: O2
SIEMENS AG
6SG7000-0BA76
SIMOTRAS HD
Operating Instructions
01.04
See
Change
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online