Power Module Error Types; Digital Electronic Module Error Types - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Commissioning and Diagnostics

Power module error types

The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-13 Power module error types
Power modules electronic
modules
PM-E 24–48
PM-E
VDC/
24 VDC
120–230 VAC
PM-E
24–48 VDC
–––

Digital electronic module error types

Table 6-14 Digital electronic module error types
Digital electronic
modules
2DI 24 VDC High
Feature
4DI 24 VDC High
Feature
6-42
Error type
17
10001: Sensor or load
D
voltage missing
18
10010: Fuse
D
defective
Error type
1
00001: Short circuit
D
1
00001: Short circuit
D
(In connection with
IM151-1 BASIC /
IM151-1 STANDARD, as
of
6ES7151-1AA02-0AB0,
IM151-1 FO
STANDARD, as of
6ES7151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
26
11010: External fault
D
(In connection with
IM151-1 STANDARD, up
to
6ES7151-1AA01-0AB0
or IM151-1 FO
STANDARD, up to
6ES7151-1AB00-0AB0)
Meaning
No supply voltage,
or inadequate
supply voltage.
The fuse in the
power module has
tripped.
Meaning
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
ET 200S Distributed I/O System
EWA-4NEB780602402-09
What to do
Correct the process
wiring. Check the
supply voltage.
Replace the fuse.
What to do
Correct the process
wiring (sensor
wiring).
Correct the process
wiring (sensor
wiring).

Advertisement

Table of Contents
loading

Table of Contents