Scalar i2000 User's Guide
With the maximum number of tape drives operating in a normal data
center environment, you should check the filters every two years. If you
see dust and debris on the inlet side of the filters, remove the filters and
use water and a mild soap to clean them. The materials in the filters should
last for the life of the product. However, if abnormal contamination
occurs, you should replace them. To order filters, contact your service
representative.
Removing an Air Filter
Use these instructions to remove either a top or bottom air filter.
Required tools: #1 Phillips screwdriver
FRU ID: 1001 (air filter)
1 Take the library offline.
For information about taking the library offline, see
Library's State
on page 380.
2 On the operator panel, press Robotics Enabled to turn off power to
the picker and return it to the home position.
The power is on to all other components.
3 Open the access door.
Aisle power is disabled.
Chapter 5 Maintaining Your Library
Maintenance Actions