CHAPTER 17
Installing the Mounting Hardware
Installing the MX2020 Mounting Hardware for a Four-Post Rack or Cabinet
Installing Cage Nuts, If Needed
Copyright © 2015, Juniper Networks, Inc.
Installing the MX2020 Mounting Hardware for a Four-Post Rack or Cabinet on page 205
Installing Cage Nuts, If Needed on page 205
1.
Installing the Four-Post Mounting Shelf on page 207
2.
Insert cage nuts, if needed, into the holes listed in
Table 77 on page
206. The hole distances are relative to the standard U division on the
rack that is aligned with the bottom of the mounting shelf.
To install cage nuts in a four-post rack:
On the rear side of both rack rails, insert cage nuts in the holes specified for the
1.
four-post mounting shelf. Install the cage nuts in the front of the front rail (see
Table 76 on page
205).
On the front side of both rack rails, insert cage nuts in the holes specified for mounting
2.
the chassis. Install the cage nuts in the front of the front rail (see
Table 76: Mounting Hole Locations for Installing the Four-Post Mounting
Shelf
Hole
Distance Above U Division
6
3.25 in. (8.3 cm)
5
2.63 in. (6.7 cm)
4
2.00 in. (5.1 cm)
3
1.50 in. (3.8 cm)
2
0.88 in. (2.2 cm)
Table 76 on page 205
and
Table 77 on page
206).
1.86 U
1.5 U
1.14 U
0.86
U
0.50
U
205