• 80070301-0301xxxx : Sensor [SensorElementName] has transitioned to non-recoverable from a
less severe state. (CPU 1 OverTemp)
This message is for the use case when an implementation has detected a Sensor transitioned to non-
recoverable from less severe.
May also be shown as 800703010301xxxx or 0x800703010301xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of
the server), that the air baffles are in place and correctly installed, and that the server cover is installed
and completely closed. 2. Check the ambient temperature. You must be operating within the
specifications (see Features and specifications for more information). 3. Make sure that the heat sink
for microprocessor n. 4. (Trained technician only) Replace microprocessor n. (n = microprocessor
number)
• 80070301-0302xxxx : Sensor [SensorElementName] has transitioned to non-recoverable from a
less severe state. (CPU 2 OverTemp)
This message is for the use case when an implementation has detected a Sensor transitioned to non-
recoverable from less severe.
May also be shown as 800703010302xxxx or 0x800703010302xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of
the server), that the air baffles are in place and correctly installed, and that the server cover is installed