ALP 8
CONTINUED 1
Is the expansion valve pipe hot at the inlet and outlet?
Is the evaporator pipe hot at the inlet and outlet?
Check fuse F01 of component 597.
Is the result of the check correct?
AFTER REPAIR
MR-453-X79-62C000$080.mif
V1
CLIMATE CONTROL
Fault finding – Fault finding chart
A
NO
NO
YES
1
Carry out a full check with the diagnostic tool.
Replace the expansion valve (see MR
451 Mechanical, 62A, Air
YES
conditioning, Expansion valve:
Removal - Refitting).
YES
Replace the evaporator.
Replace the faulty fuse (see MR 451
NO
Mechanical, 81C, Fuses, Fuses: List
and location of components).
62C-51
62C