May also be shown as 800102041d04ffff or 0x800102041d04ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix: PLAT ID: 0480
User Response
1. Reseat the failing fan indicated by the lit LED on the fan.
2. Replace Fan.
Related links
– Removing a hot-swap fan assembly
• 80010204-1d05ffff : Numeric sensor [NumericSensorElementName] going low (lower critical) has
asserted.
IMM has detected the speed of Fan 5A or Fan 5B has gone low.
May also be shown as 800102041d05ffff or 0x800102041d05ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix: PLAT ID: 0480
User Response
1. Reseat the failing fan indicated by the lit LED on the fan.
2. Replace Fan.
Related links
– Removing a hot-swap fan assembly
• 80010204-1d06ffff : Numeric sensor [NumericSensorElementName] going low (lower critical) has
asserted.
IMM has detected the speed of Fan 6A or Fan 6B has gone low.
May also be shown as 800102041d06ffff or 0x800102041d06ffff