Lenovo System x3850 X6 Installation And Service Manual page 593

Hide thumbs Also See for System x3850 X6:
Table of Contents

Advertisement

12
CIM Information
Prefix: PLAT ID: 0520
User Response
Complete the following steps until the problem is solved:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that all baffles included with the system are installed.
5. Check the heatsink on the ML2 card to ensure that it is free of particulates and dust which would
reduce cooling efficiency.
6. Remove the heatsink on the ML2 card, check to make sure there is good contact between the
heatsink and chip, and then reinstall the heatsink.
Related links
– Server features and specifications
– Removing and replacing components
– Thermal grease
• 80070107-0301ffff : Sensor [SensorElementName] has transitioned from normal to non-critical
state.
The Compute Book 1 has been removed from the system. System power blocked.
May also be shown as 800701070301ffff or 0x800701070301ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Other
SNMP Trap ID
60
CIM Information
Prefix: PLAT ID: 0520
User Response
Install the Compute Book 1 with fans to allow proper cooling to the PCH and FPGA chips.
Related links
– Replacing a compute book
– Removing a compute book
• 80070107-0302ffff : Sensor [SensorElementName] has transitioned from normal to non-critical
state.
The Compute Book 2 has been removed from the system
May also be shown as 800701070302ffff or 0x800701070302ffff