Mounting To The Plc - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Mounting to the PLC

3-5
Mounting to the PLC
CS-series PLCs
FL-net Units can be mounted to any slots in either a CS-series CPU Rack or a
CS-series Expansion Rack, but the number of slots to which they can be
mounted depends on the Backplane. Up to four FL-net Units can be mounted
to a single PLC. If an FL-net Unit is mounted in combination with other CPU
Bus Units (e.g., Controller Link Units), the maximum total number of CPU Bus
Units that can be mounted is 16.
Note PLC Backplane mounting screws to a torque of 0.9 N⋅m, and the Unit's
mounting screws to a torque of 0.4 N⋅m.
CS1W-BC023/033/053/083/103 Backplane
2, 3, 5, 8, or 10 slots (Expansion Backplane not
possible with 2-slot CPU Backplane.)
CS1W-B1033/053/083/103 Expansion Backplane for CS Series
3, 5, 8, or 10 slots
Expansion I/O Backplane for C200H Series
Note The current consumption of the CS1W-FLN22 FL-net Unit is 380 mA maxi-
mum. Make sure that the total current consumption of all Units mounted to the
CPU Rack or Expansion Rack to which the FL-net Unit is mounted does not
exceed the capacity of the Power Supply Unit.
CS-series CPU Rack
Can mount to any
position with 2, 3, 5, 8,
or 10 slots.
CS-series Expansion Rack
Can mount to any position
with 3, 5, 8, or 10 slots.
C200H-series I/O
Expansion Rack
Can mount to any slot
position.
CPU: CPU Unit
PS: Power Supply Unit
Section 3-5
Up to four Units can
be mounted to the
slots shown in the
diagram to the left.