Mounting To The Backplane - Omron SYSMAC CS1G Operation Manual

Motion control unit
Table of Contents

Advertisement

Installation
3-2-2

Mounting to the Backplane

1,2,3...
Note
Use the following steps to mount or remove MC Units.
1. Mount the Unit on the Backplane by hooking the top of the unit into the slot
on the Backplane and rotating the Unit downwards.
Hook
2. Make sure that the connector on the back of the Unit is property inserted
into the connector on the Backplane.
3. Use a Phillips screwdriver to tighten the screw on the bottom of the Unit.
The screwdriver must be held at a slight angle, so be sure to leave enough
space below the rack.
Duct
20 mm min.
CPU Unit
I/O Power
Supply Unit
Slave Rack
20 mm min.
Duct
Phillips screwdriver
Tighten the screw to a torque of 0.4N-m.
To remove the Unit, loosen the screw with a Phillips screwdriver, rotate the
Unit upwards, and then remove it.
Backplane
Backplane
Section 3-2
33