Allocated Words in the CIO Area

Note
4-3
Allocated Words in the CIO Area
Offset
D15
n
n+1
n+2
3. Internode test response monitoring time
n+3
4. Internode test status
n+4
6. Number of internode test timeout
errors
n+5
8. Number of internode test
transmission errors
n+6
n+7
n+8
n+9
n+10
n+11
n+12
n+13
n+14
n+15
13. Node connection information (256 nodes)
n+16
n+17
n+18
n+19
n+20
n+21
n+22
1. To circulate a token among the nodes connected to the network, match the
uppermost three digits of the IP address, the sub-net mask, and the broad-
cast type to those of the other connected nodes.
2. If either Unit rear rotary SW + node No. or Unit rear rotary SW is set as the
IP address setting method for the CS1W-FLN22 or CJ1W-FLN22, a setting
error will occur (HER indicator will light). Set the IP address setting method
to either 192.168.250 + node No. (default) or Setup Area.
3. The baud rate setting is supported by the CS1W-FLN22 and CJ1W-FLN22
only. The setting cannot be made for the CS1W-FLN02 or CS1W-FLN12,
which always communicate at 10 Mbps.
4. Select Option - Switch Settings - Hex from the Main Menu. The IP ad-
dress and subnet mask will be displayed in hexadecimal, and hexadecimal
input will be possible.
5. If communications are set to connect via the network and storage in the
PLC is set to use the FA link allocation table storage method, the maximum
number of nodes that can be registered in other node areas is 50.
Data is stored from the beginning word in the area for each Unit, according to
the offset positions shown in the following table.
Beginning word n can be calculated by means of the following equation.
Beginning word n = 1,500 + (25 x unit number):
D8
D7
1. Unit control bits
2. Internode test destination address
5. Number of internode test runs
7. Number of internode test
9. Number of times internode test data
10. Unit status
11. Network status
12. Refresh cycle time
D0
Data direction
CPU Unit ↔ FL-net Unit
CPU Unit to FL-net Unit
FL-net Unit to CPU Unit
response errors
did not match
FL-net Unit to CPU Unit
Section 4-3
51