Omron CS1W-FLN22 Operation Manual page 168

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Internode Test
Setting the Test Parameters
Configuration of the test
parameters
Setting Range
Starting and Stopping the Internode Test
142
3. If desired, the test parameters can be changed while the internode test is
actually running. Use the same procedure as used in step 1.
4. Turn OFF the Internode Test Start Bit allocated to the FL-net Unit in the
CPU Bus Unit Area to stop the test.
Note
1. The test parameters are effected as soon as they are set or changed. It is
not necessary to reboot or restart. If the test parameters are changed dur-
ing the test, however, the new parameters will not be used until the Intern-
ode Test Start Bit is turned OFF and then back ON.
2. Line traffic on the Ethernet network will increase during the test, possibly
affecting system performance.
Before starting the test, set the following parameters in the CPU Bus Unit
Area (in the CIO Area) of the PLC. The test parameters become effective
immediately after they are set. It is not necessary to reboot or restart the PLC.
The software switches are stored at offsets from the first word calculated with
the formula: first word = 1500 + (25 × unit number + offset)
The parameter setting ranges are given in the following table.
Offset
+1
Remote network address
+2
Response monitoring time
(unit: 10 ms)
Note
1. The test cannot run across a FINS network.
2. Broadcast transmissions (target node address = FF) cannot be used for
the internode test.
3. A timeout error will occur if no response is received within the set response
monitoring time.
Bit 01 of the first word in the words allocated to the FL-net Unit in the CPU
Bus Unit Area is used as the Internode Test Start Bit. Turn ON bit 01 to start
the internode test and turn bit 01 OFF to stop the internode test. The address
of the word containing the Internode Test Start Bit is calculated by the follow-
ing formula:
Word = 1500 + (25 × unit number)
15
14
Bit
The internode test run status can be confirmed using the TS indicator on the
Unit's front panel.
TS indicator
Lit
Not lit
Parameter
13
12
11
10
9
8
Run status
Internode test running
Internode test stopped
Section 9-3
Settable range
01 to F9 Hex (1 to 249 decimal)
0000 Hex: 2 sec.s
0001 to FFFF Hex (1 to 65535
decimal)
7
6
5
4
3
2
Internode Test Start Switch
0: Stop internode test
1: Start internode test
1
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-fln22