Error Log Error Codes - Omron CS1W-FLN22 Operation Manual

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Error Log
Error Log Table
Error Log Location
FINS Commands for Error
Logs

10-3-2 Error Log Error Codes

Error
Meaning
code
0001
Watchdog timer error in CPU Unit 00
0002
CPU Unit service monitor error
0006
Other CPU error
000F
CPU Unit initialization error
0010
Insufficient System Setup Area
0011
Event timed out
0012
CPU Unit memory error
0013
CPU Unit protected
0040
Self-removal
150
Each error is recorded as one record in an error log table. Up to 64 records
can be saved. If more than 64 errors occur, the oldest errors will be deleted
from the error log and the most recent error will be recorded.
The following information is recorded in the error log table.
• Main error code (See table later in this section.)
• Detailed error code (See table later in this section.)
• Time stamp (from the clock in the CPU Unit)
When an error is detected, the error codes and time stamp are recorded in the
error log in RAM inside the FL-net Unit. Serious errors are also recorded in
EEPROM. The maximum number of errors that can be saved to EEPROM is
32. The errors recorded in EEPROM will be saved even if the Unit is restarted
or power is turned OFF. When the FL-net Unit is started, the contents of the
error log in EEPROM are copied to RAM.
When a FINS command is used to read the error log, the log held in RAM is
read. The error log cannot be cleared.
The FL-net Unit's error log can be read using the CX-FLnet or FL-net Unit
Support Software. The following FINS commands can also be used to read or
clear the error log. For details on each command, refer to 7-5 Command/
Response Reference.
Command
code
MRC
SRC
21
02
ERROR LOG READ
The error codes are described in the following table. The detailed error code
will provide detailed information on an error.
Detailed error code
1st byte
00
monitoring time (ms)
Bit 11: Unit not in Registered
I/O Tables
00
00
00
00
01: Read
03: Routing
error
table
02: Write
04: Setup
error
error
05: CPU Bus
Unit Words
(CIO/DM)
00
00
Undefined
Function
Correction
2nd byte
Replace the CPU Unit.
Check the operating environment. Saved
Create the I/O tables.
Replace the CPU Unit.
Reduce the number of CPU Bus
Units.
Replace the CPU Unit.
01: Recreate the data specified by
the 2nd byte of the detailed error
code.
02: Clear memory using proce-
dure in the PLC operation manual.
Remove protection from CPU Unit
memory.
Check the communications cable
hub connection. Use the CX-
FLnet or FL-net Unit Support Soft-
ware to increase the value for the
minimum allowable frame interval.
Section 10-3
EE-
PROM
Saved
Saved
Saved
Saved
Saved
Saved
Saved
---